Rosemount Raptor
Section 5. Installing a Raptor Level Gauging System
6. In the 2410 Tag drop-down list choose the Rosemount 2410 Tank Hub
that the 5300 radar is connected to.
7. Enter the Modbus address that is used for the 5300. Note that this
address must be stored in the 2160 FCU Slave Database as well as in
the 2410 Tank Database.
8. Click the Verify Communication button to verify that the TankMaster PC
communicates with the 5300. The Unit ID will appear when contact is
established.
9. Verify the tank position. The Position in 2410 HUB field shows the tank
position that the 5300 is mapped to in the 2410 tank database. The tank
position indicates which tank the 5300 is associated with. In case the
5300 radar is connected to a multiple tank version of the Rosemount
2410, the 5300 can be mapped to another tank position via the 2410
Tank Hub Properties/Tank Database window if necessary (in the
WinSetup workspace, click the right mouse button on the 2410 icon and
choose the Properties option).
See “Tank Database Setup” on page 5-42 for more information on how to
configure the 2410 Tank Database.
10. Click the Next button to proceed with the 5300 configuration.
11. For configuration of the 5300 GWR Probe window refer to the
appropriate parts in “Configuration via 5300 Properties” on page 5-91.
12. For configuration of the 5300 GWR Environment window refer to the
appropriate parts in “Advanced Configuration” on page 5-99.