Emerson 300510EN Yogurt Maker User Manual


 
System Configuration Manual
300510EN, Rev AA
December 2010
Rosemount Raptor
5-4
Section 5. Installing a Raptor Level Gauging System
4 Installation and Configuration of Rosemount 2410 Tank Hub
The Rosemount 2410 should be installed after the Rosemount 2160 Field
Communication Unit. In case the Rosemount 2410 is connected directly to
a TankMaster work station without a 2160 FCU, the 2410 has to be
installed before the other field devices. To install a 2410 do the following:
Specify a device tag
Assign a Modbus communication address
Configure the 2410 Tank Database which maps devices to tanks
Configure the optional local display
5 Installation and Configuration of Field Devices
When setting up a Raptor level gauging system the field devices, such as
level gauges and temperature transmitters, are installed in TankMaster
Winsetup as part of the Rosemount 2410 installation procedure. The
devices are configured at a later stage by using the Properties window of
each device.
Installation and configuration of devices include the following steps:
6 Installation and Configuration of Tanks
Installing a tank includes the following steps:
7Calibration
When a Rosemount 5900S Radar Level Gauge is installed and configured
the Calibration Distance may have to be adjusted in order to match
measured level and actual product level. The adjustment should be
performed once at the final commissioning.
Communication Specify protocol and address.
Configuration Specify tank geometry parameters, device specific
parameters, temperature element positions, and
other parameters depending on the device type.
Choose tank type Select one of the available options such as Fixed
Roof, Floating Roof, Sphere LPG, Horizontal LPG,
or other suitable tank type.
Specify a tank tag Specify a name to be used as an identifier in the
Workspace window and other TankMaster
windows.
Select devices Associate devices to the tank.
Configuration Specify the available source signals for parameters
such as Free Water Level, Vapor Pressure and
Liquid Pressure.
Value Entry Specify an approved value range for each
measurement variable. In case there is no source
instrument available for a certain parameter, you
can specify manual values to be used instead.