5.16 SETTING UP A
HYBRID SYSTEM
This is a description of how to install a Rosemount Raptor on-line density
measurement system to be used for mass calculations. Before starting the
setup make sure the 2160 FCU Slave Database is configured accordingly,
see “Installing a Rosemount 2160 FCU” on page 5-25.
For the mass calculations to work properly, a tank strapping table (also
refered to as a Tank Capacity Table) must be entered, see the TankMaster
WinOpi Reference Manual, Document No. 303028EN for more information.
A Rosemount Raptor hybrid system typically includes two pressure sensors,
P1 and P3, and a Rosemount 5900S Radar Level Gauge. To configure the
system do the following:
1. Start the TankMaster WinSetup program.
2. In the Workspace window select the tank server icon (This Workstation in
the example below):
3. Click the right mouse button and select Setup, or choose menu option
Service>Servers>Setup to open the Server Preferences window.
4. Select the Units tab.
5. Choose the desired measurement units for Density and Pressure.
6. Click the Apply button to store the settings.
7. Select the Inventory tab.
Pressure
Density