System Configuration Manual
300510EN, Rev AA
December 2010
Rosemount Raptor
5-120
Section 5. Installing a Raptor Level Gauging System
12. Type a name in the Tank Name field. This tank name should also be
used at a later stage when installing the tank to be associated with the
current 2410 Tank Hub, see “Installing a Tank” on page 5-101.
13. The Level Modbus Address field is enabled for the new level gauge.
Specify a Modbus address of your own choice. Note that it must be the
same Modbus address as configured in the 2160 FCU Slave Database
for this level gauge.
14. In case a non-level Auxiliary Tank Device (ATD) such as a Rosemount
2240S Multi-input Temperature Transmitter is installed, the ATD Modbus
Address field is enabled as well.
Specify a Modbus address of your own choice. Note that it must be the
same Modbus address as configured in the 2160 FCU Slave Database.
For tank position 1, the ATD Modbus address is automatically configured
as the Modbus address of the Rosemount 2410 Tank Hub itself. All the
non-level devices on a tank are represented by a single ATD device in
the Rosemount Raptor system.
See “Installing a Rosemount 2160 FCU” on page 5-25 and “Examples of
2160 FCU Slave Database Configuration” on page 5-32 for further
information on how to configure the 2160 FCU slave database and the
tank database in the 2410 Tank Hub.
15. Click the Apply button to store the tank database configuration.
16. Select the Device Tags tab: