System Configuration Manual
300510EN, Rev AA
December 2010
Rosemount Raptor
7-18
Section 7. Service Functions
7.9 UPGRADING THE
DEVICE
SOFTWARE
TankMaster WinSetup allows you to upgrade the software of Rosemount
Raptor level gauges and other devices.
To upload new software do the following:
1. Make sure the devices are properly prepared for reprogramming.
2. In the WinSetup Workspace, select the Devices folder, or select a
specific device in the Devices folder.
3. Click the right mouse button and choose the Program All option, or from
the Service menu choose Devices>Program All.
(For a single device, choose the Program option, or from the Service
menu, choose the Devices>Program option).
4. Select the device to be programmed from the Available Devices pane
and click the Move button. Repeat for each device to be programmed.
Note that if a single device was selected in the Workspace window, it will
appear automatically in the Program These Devices pane.
Use the Remove button if you would like to change the list of devices to
be programmed.
5. Click the Browse button to locate the appropriate software file.
6. Click the Start Programming button to open the Start Device
Programming window: