5-58
Section 5. Installing a Raptor Level Gauging System
5.7.2 Installing a 5900S
Using the
Installation
Wizard
The installation wizard in TankMaster WinSetup is a tool that may be used to
install and configure a Rosemount 5900S Radar Level Gauge and other
devices.
However, in most cases the following procedure is recommended when
installing a new Rosemount 5900S gauge:
1. Add the new 5900S Radar Level Gauge to the Rosemount 2160 FCU
Slave Database. Ensure that the correct Modbus address is configured
(see “Installing a Rosemount 2160 FCU” on page 5-25 for more
information).
2. Configure the Tank Database in the 2410 Tank Hub Properties/
Tank Database window, (see “Installing a Rosemount 2410 Tank Hub” on
page 5-38 for more information).
3. Install the 5900S in TankMaster via the 2410 Tank Hub Properties/
Device Tags window.
4. Configure the 5900S (see “Configuration via the Properties Window” on
page 5-52).
See also “Adding a Tank to a Raptor System” on page 5-114 for further
information on adding tanks and devices to a Raptor system.
In case the recommended installation procedure as described above can not
be used, the installation wizard offers an alternative method to install a new
Rosemount 5900S level gauge in TankMaster. In this case do the following:
1. Configure the Rosemount 2160 Slave Database by including the new
5900S Radar Level Gauge. Ensure that the correct Modbus address is
configured (see “Installing a Rosemount 2160 FCU” on page 5-25 for
more information).
2. Configure the Rosemount 2410 Tank Database in the 2410 HUB
Properties/Tank Database window, (see “Installing a Rosemount 2410
Tank Hub” on page 5-38 for more information).
3. Install and configure the Rosemount 5900S as described in “Using the
installation wizard” on page 5-59.