Section 5. Installing a Raptor Level Gauging System
5.12 ADDING A TANK TO A RAPTOR SYSTEM
New tanks can easily be added to a Raptor system. The procedure will be
slightly different depending on the specific system configuration. It can be
summarized as follows:
Option 1. Installing a new Rosemount 2410 Tank Hub and a new tank.
1. Configure the communication settings of the 2160 Field Communication
Unit (FCU).
2. Update the 2160 FCU Slave Database by adding the field devices to be
associated with the new tank.
3. Install the new Rosemount 2410 Tank Hub and configure the Tank
Database by mapping the field devices to the new tank.
4. Configure the new field devices added to the 2410 tank database
(Rosemount 5900S, Rosemount 2240S, Rosemount 3051S etc.).
5. Configure the new tank.
Figure 5-12. A new tank and
2410 Tank Hub are added to the
workspace
Option 2. Adding a new tank to an existing Rosemount 2410 Tank Hub.
1. Update the 2160 FCU Slave Database by adding the field devices
installed on the new tank.
2. Update the tank database of the existing Rosemount 2410 Tank Hub by
mapping the new field devices to the new tank.
3. Configure the field devices added to the 2410 tank database.
4. Configure the new tank.
Figure 5-13. A new tank is
added to an existing 2410
tank hub
Detailed descriptions of the two procedures outlined above are provided in
sections “Adding a New Tank and a New 2410 Tank Hub” on page 5-115 and
“Adding a New Tank to an Existing 2410 Tank Hub” on page 5-117.