Rosemount Raptor
Section 5. Installing a Raptor Level Gauging System
7. Configure the Slave Database.
The FCU Slave Database ensures that the 2160 FCU requests
information from all the connected field devices. The 2160 FCU is
compatible with the TRL2 and Rex systems. Therefore, two Modbus
addresses are used for each tank. Each position in the FCU Slave
Database represents one tank. Positions 1A to 32A are used for level
gauges such as the Rosemount 5900S and other supported level
gauges. Positions 1B to 32B are used for Rosemount 2410 Tank Hubs
and Auxiliary Tank Devices (ATDs) such as the Rosemount 2240S
Multi-input Temperature Transmitter.
It is very important that the 2160 FCU Slave Database is properly
configured to allow communication between the Rosemount 2160 Field
Communication Unit, the Rosemount 2410 Tank Hub, and the field
devices such as level gauges and other devices.
NOTE!
Once all devices and tanks are installed and configured, the position of a
device in the Slave Database may not be changed, since this will result in
corrupt mapping of tank to Slave Database position.
1. Select Slave Type=2410
Level for level gauges
connected to the 2410
2. Slave Type=2410 Temp is
automatically assigned for
temperature transmitters and
other auxiliary devices