System Configuration Manual
300510EN, Rev AA
December 2010
Rosemount Raptor
5-92
Section 5. Installing a Raptor Level Gauging System
3. Select the Communication tab.
4. Verify the position in the tank database. The Connected to HUB field
shows the name of the 2410 Tank Hub and the tank position that the
5300 is mapped to in the 2410 tank database. The tank position indicates
which tank the 5300 is associated with.
In case the 5300 radar is connected to a multiple tank version of the
Rosemount 2410, the 5300 may be mapped to another tank position via
the 2410 Tank Hub Properties/Tank Database window if necessary (in
the WinSetup workspace, click the right mouse button on the 2410 icon
and choose the Properties option).
See “Tank Database Setup” on page 5-42 for more information on how to
configure the 2410 Tank Database.
5. Verify that the Modbus address is correct. To change the Modbus
address click the Change button.
a. Enter the Unit ID in the Unit ID input field.
When changing the device address, the Unit Id is used as a unique
identifier of the device. The Unit Id can be found on a label mounted
on the device.
b. Set the desired address in the Set Modbus Address input field.
c. Click the OK button to confirm the settings and to close the Change
Address window.
6. Click the Apply button to store the configuration.