Section 5. Installing a Raptor Level Gauging System
4. Verify the tank position. The Connected to HUB field shows the name of
the 2410 Tank Hub and the tank position that the 5400 is mapped to in
the 2410 tank database. The tank position indicates which tank the 5400
is associated with.
In case the 5400 transmitter is connected to a multiple tank version of the
Rosemount 2410, the 5400 may be mapped to another tank position via
the 2410 Tank Hub Properties/Tank Database window if needed (in the
WinSetup workspace, click the right mouse button on the 2410 icon and
choose the Properties option).
See “Tank Database Setup” on page 5-42 for more information on how to
configure the 2410 Tank Database.
5. Verify that the Modbus address is correct. To change the Modbus
address click the Change button:
a. Enter the Unit ID in the Unit ID input field.
When changing the device address, the Unit Id is used as a unique
identifier of the device. The Unit Id can be found on a label mounted
on the device.
b. Set the desired address in the Set Modbus Address input field.
c. Click the OK button to confirm the settings and to close the Change
Address window.
6. Click the Apply button to store the configuration, or click the OK button
to store the configuration and close the window.