Rosemount Raptor
5-60
Section 5. Installing a Raptor Level Gauging System
6. In the 2410 Tank HUB Tag drop-down list choose the Rosemount 2410
Tank Hub that the 5900S Radar Level Gauge is connected to. Normally,
there is one 2410 for each tank equipped with a 5900S Radar Level
Gauge.
7. Enter the Modbus address that is used for the 5900S Radar Level
Gauge. This address must also be stored in the 2160 FCU Slave
Database as well as in the 2410 Tank Database.
8. Click the Verify Communication button to verify that the TankMaster PC
communicates with the 5900S Radar Level Gauge. The Unit ID will
appear when contact is established.
9. Check the Position in 2410 HUB field to verify that the 5900S is mapped
to the correct tank position in the 2410 tank database. Normally, the
single tank version of the Rosemount 2410 Tank Hub is used for
Rosemount 5900S level gauges. In this case the Position in 2410 HUB
field will be equal to 1 since there is only one tank position that is used in
the 2410 Tank Database.
In case the multiple tank version of the 2410 Tank Hub is used to handle
several tanks, the level gauge can be mapped to the desired tank via the
2410 Tank Hub Properties/Tank Database window (in the WinSetup
workspace, click the right mouse button on the 2410 icon and choose the
Properties option).
See “Tank Database Setup” on page 5-42 for more information on
2410 Tank Database setup.
10. Click the Next button to proceed with the 5900S configuration.
11. For descriptions of the 5900S RLG Antenna and the 5900S RLG
Geometry windows, refer to the appropriate parts in chapter
“Configuration via the Properties Window” on page 5-52.