System Configuration Manual
300510EN, Rev AA
December 2010
Rosemount Raptor
7-4
Section 7. Service Functions
7.3 USER DEFINED TEMPERATURE CONVERSION
The Rosemount 2240S Multi-input Temperature Transmitter supports the use
of non-standard spot temperature sensors. For these type of temperature
elements you can specify the relation between temperature and electrical
resistance with tables or mathematical formulas.
To enable and configure the different conversion methods:
1. In the WinSetup workspace, select the ATD device icon.
2. Click the right mouse button and choose the Properties option.
3. In the 22XX ATD window, select the 2240S MTT Temperature Sensor
tab:
4. Disable Use Auto Sensor Configuration.
5. In the Conversion Method scroll menu, choose one of the user defined
conversion methods.
6. Click the configuration button that corresponds to the selected user
defined conversion method.
Choose
conversion
method
Click to
configure
Disable the
Auto Sensor
Configuration