System Configuration Manual
300510EN, Rev AA
December 2010
5-41
Rosemount Raptor
Section 5. Installing a Raptor Level Gauging System
9. To verify communication with the 2410 Tank Hub, type the current
Modbus address and click the Verify Communication button. The Unit
Id will appear if the correct Modbus address was entered (the 2410 is
shipped with the default Modbus address=247).
In case you would like to change the current Modbus address, or the
address is unknown, click the Change Address on Device button.
NOTE!
In case several 2410 Tank Hubs are connected using the same default
address (247), you will have to change the addresses before the Verify
command can be used. See ”How to change the Modbus address of the
2410” for more information.
How to change the Modbus address of the 2410
a. In the 2410 Tank Hub Communication window click the Change
Address on Device... button to open the Change Address window.
b. Enter the Unit ID and the new Modbus Address
When changing the device address, the Unit Id is used as a unique
identifier of the device. The Unit Id can be found on a label mounted
on the device.
Tip! If there is no other device connected that uses the same
address as the current device, you can find the Unit Id by typing the
current address into the Address field in the 2410 Tank Hub
Communication window and clicking the Verify Communication
button.
c. Click the OK button to confirm the address settings and close the
Change Address window.
d. In the 2410 Tank Hub Communication window click the Verify
Communication button to check that communication is established
between the TankMaster work station and the 2410 Tank Hub. The
Unit ID will appear when TankMaster finds the 2410.
10. In the 2410 Tank Hub Communication window click the Next button to
continue the installation procedure of the 2410.