5-33
Rosemount Raptor
Section 5. Installing a Raptor Level Gauging System
For each level gauge the 2410 Level address in the 2160 FCU Slave
Database must be equal to the Level Modbus address in the 2410 Tank
Database.
In this example the Level Modbus address for tank TK-1 is entered in
position 1A in the 2160 FCU Slave Database and in tank position 1 in the
2410 Tank Database.
The Level Modbus address for tank TK-2 is entered in position 2A in the 2160
FCU Slave Database and in tank position 1 in the 2410 Tank Database.
Figure 5-4 illustrates how to configure the 2160 FCU and the two 2410 Tank
Hubs for the two level gauges on tanks TK-1 and TK-2:
Figure 5-4. The same Level
device address must be
configured in the 2160 Slave
Database and the 2410 Tank
Database
2410 TANK DATABASE: TK-1
2410 TANK DATABASE: TK-2
2160 FCU SLAVE DATABASE