Section 5. Installing a Raptor Level Gauging System
11. For still pipe applications select the Enable still pipe/Bridle
Measurements check box and enter the Pipe Inner Diameter.
See the Rosemount 5400 Reference Manual (Document No.
00809-0100-4026) for more information on Hold Off Distance and other
transmitter parameters.
12. Click the Apply button to store the configuration.
13. Select the Geometry tab.
14. Enter the tank distance parameters.
a. Tank Reference Height (R).
The Tank Reference height (R) is defined as the distance from the
Tank Reference Point to the Zero Level.
b. Reference Distance (G).
The Reference Distance (G) is the distance between the Tank
Reference Point and the Gauge Reference Point, which is located at
the top surface of the nozzle flange on which the gauge is mounted.