Emerson 300510EN Yogurt Maker User Manual


 
System Configuration Manual
300510EN, Rev AA
December 2010
5-117
Rosemount Raptor
Section 5. Installing a Raptor Level Gauging System
5.12.2 Adding a New
Tank to an
Existing 2410
Tank Hub
In case the new devices are connected to an existing 2410 Tank Hub, you will
have to update the 2410 tank database, and install and configure the new
devices in TankMaster WinSetup.
1. Start the TankMaster WinSetup program.
2. Open the 2160 FCU Properties window.
3. Select the Slave Database tab.
4. Configure the Slave Database with Modbus addresses of the new level
gauge and ATD devices, see “Installing a Rosemount 2160 FCU” on
page 5-25 for more information.
5. In the WinSetup Workspace, select the 2410 Tank Hub icon:
6. Click the right mouse button and choose the Properties option, or from
the Service menu choose Devices>Properties.