System Configuration Manual
300510EN, Rev AA
December 2010
Rosemount Raptor
7-16
Section 7. Service Functions
7.8.2 To Save Device
Registers
Multiple Devices
To save a backup copy of the current configuration for multiple devices, do the
following:
1. In the TankMaster WinSetup workspace, select the Devices folder.
2. Click the right mouse button and choose the Save Database of All to
Files option, or from the Service menu choose Devices>Save
Database of All to Files.
3. Select a device from the Available Devices pane and click the Add
button in order to move it to the Selected Devices pane. Repeat for all
devices you would like to include.
4. Select Holding registers.
5. Choose the Predefined Registers or the User-Defined option.
The Predefined option stores the most frequently used registers.
The User-defined option stores a specified range of Holding registers
and should only be used for advanced service.
6. Click the Browse button, select a folder and type a file name.
7. Click the Start button to save the database backup.
Input Registers can also be saved on disk for service and troubleshooting:
1. Select the devices you would like to include.
2. Select Input Registers.
3. Choose the Predefined Registers or the User-Defined option.
The Predefined option stores the most frequently used registers.
The User-defined option stores a specified range of Holding registers
and should only be used for advanced service.
4. Click the Browse button and select a folder and a file name.
5. Click the Start button to save the file.