System Configuration Manual
300510EN, Rev AA
December 2010
Rosemount Raptor
5-34
Section 5. Installing a Raptor Level Gauging System
The 2410 Temp address in the 2160 FCU Slave Database must be equal to
the ATD Modbus address in the 2410 Tank Database.
For tank TK-1 the ATD Modbus address is entered in position 1B in the 2160
FCU Slave Database and is automatically assigned to tank position 1 in the
2410 Tank Database.
The ATD Modbus address for tank TK-2 is entered in position 2B in the 2160
FCU Slave Database and is automatically assigned to tank position 1 in the
Tank Database of the second 2410 Tank Hub.
Figure 5-5 illustrates how to configure the 2160 FCU and the two 2410 Tank
Hubs for the ATD devices on tanks TK-1 and TK-2:
Figure 5-5. The same Modbus
address must be configured for
the ATD devices in the 2410
Tank Database and the 2410
Temp devices in the 2160 Slave
Database
2410 TANK DATABASE: TK-1
2410 TANK DATABASE: TK-2
2160 FCU SLAVE DATABASE
Note!
For a tank at Tank Position 1
the ATD Modbus address is
equal to the Modbus address
of the 2410 Tank Hub itself