6 - 11 6 - 11
MELSOFT
6 COMMUNICATION SETTING EXAMPLES OF THE UTILITY SETTING TYPE
(b) For 1:n communication
Settings
Module 1) Module 2)
Switch (Switch Number)
CH1 side CH2 side CH1 side CH2 side
Mode setting switch 0 5 (format 5) 5 (format 5)
Station number setting switches 1 3
Operation setting switch (SW01)
OFF (independent
operation)
ON (synchronous
operation)
OFF
(independent operation)
Data bit setting (SW02) ON (8 bit) ON (8 bit)
Parity bit yes/no setting (SW03) ON (yes) ON (yes)
Even parity/odd parity setting (SW04) OFF (odd) OFF (odd)
Stop bit setting (SW05) OFF (1 bit) OFF (1 bit)
Sum check yes/no setting (SW06) ON (yes) ON (yes)
Online change enable/disable setting
(SW07)
ON (enable) ON (enable)
Setting change enable/disable setting
(SW08)
ON (enable) ON (enable)
9600bps 9600bps
SW Setting SW Setting
SW09 ON SW09 ON
SW10 OFF SW10 OFF
SW11 ON SW11 ON
SW12 OFF SW12 OFF
Transmission speed setting
(SW09 to SW12)
Transmission
specifications
setting
switches
— (SW13 to SW15) All OFF All OFF