6 - 103 6 - 103
MELSOFT
6 COMMUNICATION SETTING EXAMPLES OF THE UTILITY SETTING TYPE
(c) Q series-compatible C24, L series-compatible C24 (When
modem communication is made on CH1 side)
Settings
Item
b15 to b8 b7 to b0
Set Value
Switch 1 CH1 communication speed CH1 transmission setting *1 0762H
Switch 2
CH1 communication protocol 0005
H
Switch 3 CH2 communication speed CH2 transmission setting *1 0000H
Switch 4
CH2 communication protocol 0000
H
Switch 5 Module station number 0000H
*1: Settings of CH1 are indicated below.
b7 b6 b5 b4 b3 b2 b1 b0
CH1 side
CH2 side
Settings
Bit Description
CH1 transmission
setting
b0 Operation setting 0 (Independent)
b1 Data bit 1 (8)
b2 Parity bit 0 (No)
b3 Odd/even parity 0 (Odd)
b4 Stop bit 0 (1)
b5 Sumcheck code 1 (Yes)
b6 Online change 1 (Enable)
b7 Setting change 0 (Disable)